*Rated voltage: 0.6/1(1.2)kV
* Max. permissible continuous operating temperature of conductor: 70oC
*Max. temperature of conductor during short-circuit (5s max. duration) shall not exceed:
*Nominal cross section of conductor ≤300mm2: 160 oC;
*Nominal cross section of conductor >300mm2: 140 oC
* The ambient temperature under installation should not be lower than: 0 oC
*The bending radius of cable is recommended as following:
*For single core cable: not less than 20 times of the diameter of cable
*For multi-core cable: not less than 15 times of the diameter of cable